Eaton PSF10I, Input voltage (Uc) 200-250VAC 1 Phase, Max Continuous Voltage 285VAC L-N, 2 Port, Portable, 300VAC L-N, 15 mins, 40dB nominal above 1MHz, 3 mode, 3 Stage Protection.
The Eaton 10 Amp Surge Protector / Inline Power Filter PSF10I is a 3-stage protection surge protector utilising high kA primary and secondary MOV protection in conjunction with an L/C filter.
We Accept
Manufacture # Eaton | Model # PSF10I
The Eaton 10 Amp Surge Protector / Inline Power Filter PSF10I is a 3-stage protection surge protector utilising high kA primary and secondary MOV protection in conjunction with an L/C filter. In addition, the PSFi also provides filtering of line harmonics and high-frequency noise with a cut-off frequency of ~10kHz and a nominal attenuation of 40dB. The PSFi series is designed to provide secondary protection against power surges caused by external sources such as lightning strikes and electrical switching as well as providing a measure of protection from surge events generated on the secondary side of the filter. The PSFi has been designed in accordance with AS3100, AS1768, IEC61643-11, IEC61000-6-1, 2, 3, 4 and other standards and codes as applicable.
Features:
Overview:
Manufacturer Warranty: 01 Years Limited Warranty
| Location Category | Indoor |
| Dimensions - Including hinges (H x W x D, mm) | 50 x 155 x 150 |
| Weight (g) | 500 |
| Warranty | 12 months |
| Input voltage (Uc) | 200-250VAC 1 Phase |
| Max Continuous Voltage (Mcov) | 285VAC L-N |
| Number of ports | 2 Port |
| Method of mounting | Portable |
| Service type | TT, TN, TN C-S or any 1 phase system with a grounded neutral. This unit must not be connected to an ungrounded system. |
| Temporary overvoltage - TOV | 300VAC L-N, 15 mins |
| Test Classification | Class II |
| Energy Absorption rating - per mode (joules) | Primary Protection L-N = 370J Primary Common Mode protection L-E & N-E = 480J Secondary protection L-N = 225J Secondary Common Mode protection L-E & N-E = 480J Aggregate rating = 1,555J |
| Current rating - continuous | 10A |
| Test Classification | Class III (IEC 61643-1), Category A (ANSI/IEEE C62.41) |
| Recommended max. overcurrent protection | 10A |
| Residual current | <0.5 mA |
| Protection modes | Line-Neutral, Line-Earth, Neutral-Earth |
| In 8/20us (Line-Neutral) Nominal surge life | 10kA x 20 hits |
| In 8/20us (Line-Earth) Nominal surge life | 3kA x 20 hits |
| In 8/20us (Neutral-Earth) Nominal surge life | 3kA x 20 hits |
| Ismax 8/20us (Line-Neutral) Max surge level | 20kA |
| Ismax 8/20us (Line-Earth) Max surge level | 10kA |
| Ismax 8/20us (Neutral-Earth) Max surge level | 10kA |
| Filter attenuation | 40dB nominal above 1MHz |
| Initial clamp voltage (Line-Neutral) | 560V |
| Initial clamp voltage (Line-Earth) | 680V |
| Initial clamp voltage (Neutral-Earth) | 680V |
| Residual voltage (Vpl) (Line-Neutral) (Let through voltage) | <1100 (3kA, 8/20uS) |
| Residual voltage (Vpl) (Line-Earth) (Let through voltage) | <1400 (3kA, 8/20uS) |
| Residual voltage (Vpl) (Neutral-Earth) (Let through voltage) | <1400 (3kA, 8/20uS) |
| Internal protection (fusing) | Thermal fusing on primary line-connected MOVs |
| Terminations | IEC 320-C14 10A input x 1, , IEC 320-C13 10A output x 1 |
| Alarms/indicators | Includes status indicators, dry contact alarm relay output (normally-closed with power applied and all SPD’s at 100% capacity). Contact rating 250Vac/32Vdc, 5A, alarm under-voltage cut off 180Vac. |
| Enclosure rating | IP42 |
| Standards. Designed in accordance with : | IEC61643-1:2005, IEC610006-1,2,3,4 ANSI/IEEE C62.41, AS/NZS1768, AS/NZS3000:2007, AS3100 |
| Environment | -10 to 65°C, 10 to 90%RH (non-condensing) |