Sku: SPD3200-TN-E
Brand: Eaton
Category: Surge Protectors
Availability: On Order
On Order - These items are sourced upon request and may take longer to deliver. We will confirm availability once your order is received, as some products may occasionally be discontinued or unavailable.
Shipping Calculator
Find
Eaton SPD3200-TN-E, 3 Phase 200ka 3 Mode Alarm Common Mode, Input 380-440vac 3P, Operating voltages 380 – 440vac 3 phase, Microprocessor control design, Provides portable power.
The SPD3200-TN-E is designed to protect three phase power systems against damage from surges and spikes caused by lightning and other electrical sources. The unit is intended for point of entry or main board protection and is connected in parallel with the power system via its own safety disconnect MCB.
We Accept
Manufacture # EATON | Model # SPD3200-TN-E
The SPD3200-TN-E is designed to protect three phase power systems against damage from surges and spikes caused by lightning and other electrical sources. The unit is intended for point of entry or main board protection and is connected in parallel with the power system via its own safety disconnect MCB.
Features:
Overview:
Manufacturer Warranty: 02 Years Limited Warranty
| Input voltage – Uc | 380-440vac 3P |
| Maximum continuous operating voltage (MCOV) | 300vac L-E |
| Temporary overvoltage - TOV | 320vac L-E |
| Service Type | TN, TN C-S 3P grounded neutral or TT 3P with no neutral |
| Test Classification (IEC61643-11) | Class I and II |
| Protection modes | L-E, N-E |
| Inom L-E | 100kA |
| Imax L-E | 200kA |
| I imp L-E | 25kA |
| Residual voltage –Vpl | <1kV at 3kA |
| <1.3kV at 20kA | |
| Safety disconnect | Series thermal fusing on SPD MOV’s |
| External disconnector | Internal 63A MCB |
| Termination sizes | 16-35mm |
| Terminations | Power terminals 16mm², Alarm terminals 1.5mm² |